Generator 150 kVA Stage V

Generator 150 kVA Stage V - product detail
Generator 150 kVA Stage V - product detail

IDEAL USAGE

Projects that require efficient and reliable temporary power, including industrial locations. 
 

APPLICATIONS

  • Temporary Power supply for projects for which connecting to an electricity grid isn’t available, such as temporary accommodations and construction or other remote sites.
  • Backup or bypass power supply during (maintenance) works in order to keep (industrial) equipment operational.
  • Additional power for (seasonal) increases in demand.
  • Standalone power supply for secondary processes.
     

BENEFITS

  • Telemetry and multiple generator synchronisation
  • Fuel efficient, proven reliability
  • Robust design
RESOURCES

Generator 150 kVA Stage V

PERFORMANCE

Electrical Features:

Main circuit breaker                     CB200A
Earth Leakage switch                   300 mA adjustable
Connections                                 1x 63 A 5p, CEE connector
                                                     1x 125 A 5p, CEE connector
                                                     1x 500 A Powersave connectors L1, L2, L3, N & Earth
                                                     Busbar 
                                                     Amphenol WCD vor gasdetection system                   

Fuel Consumption:

70% Load Prime                          22.7 L/h
70% Load Prime (AdBlue Tank)   1.4 L/h                                                   
 

Autonomy:

70% Load Prime                          30 hours
70% Load Prime (AdBlue Tank)   50 hours                                   

Typical Sound Pressure:

LpA (7 m)                                    67 dBa

Communication and Control:

Featuring:                                    Automatic load-sharing mode
                                                    Automatic pre-heating
                                                    Automatic start via timer or external contact
                                                    Oil pressure alarm
                                                    High temperature alarm
                                                    Fuel level alarm
                                                    Bund level alarm
                                                    Overload alarm
Readable data:                            Alarms and warnings
                                                    Fuel level
                                                    Engine running hours
                                                    Frequency
                                                    Voltage per phase
                                                    Amperage per phase
                                                    Power in kW and kWh
                                                    Next maintenance

WEIGHT AND MEASUREMENTS

Dimensions:

3390 mm x 1130 mm x 2390 mm (L x W x H)

Weight:

3240 kg

Capacity Fuel Tank:

700 L

Capacity AdBlue Tank:

70 L

ENGINE AND OPTIONS

Engine:

Power                                                  150 kVA
Voltage                                                230/400 V 50 Hz
Manufacturer and Model                    Bruno                 GX165V-V
Model engine                                      Volvo                  TAD880GE
Model generator                                 Leroy Somer       LSA 44.3L10
Emission Standard                               Euro Stage V

Standard Options:

  • Fuel tank with bund
  • Heavy duty base frame with tow bar
  • Central lifting eye
  • Forklift guides
  • Base frame closed at the bottom
  • Spark arrestor
  • Quick connectors for connection to external tank
DATA SHEET