Electrical Features:
Main circuit breaker CB200A
Earth Leakage switch 300 mA adjustable
Connections 1x 63 A 5p, CEE connector
1x 125 A 5p, CEE connector
1x 500 A Powersave connectors L1, L2, L3, N & Earth
Busbar
Amphenol WCD vor gasdetection system
Fuel Consumption:
70% Load Prime 22.7 L/h
70% Load Prime (AdBlue Tank) 1.4 L/h
Autonomy:
70% Load Prime 30 hours
70% Load Prime (AdBlue Tank) 50 hours
Typical Sound Pressure:
LpA (7 m) 67 dBa
Communication and Control:
Featuring: Automatic load-sharing mode
Automatic pre-heating
Automatic start via timer or external contact
Oil pressure alarm
High temperature alarm
Fuel level alarm
Bund level alarm
Overload alarm
Readable data: Alarms and warnings
Fuel level
Engine running hours
Frequency
Voltage per phase
Amperage per phase
Power in kW and kWh
Next maintenance
Dimensions:
3390 mm x 1130 mm x 2390 mm (L x W x H)
Weight:
3240 kg
Capacity Fuel Tank:
700 L
Capacity AdBlue Tank:
70 L
Engine:
Power 150 kVA
Voltage 230/400 V 50 Hz
Manufacturer and Model Bruno GX165V-V
Model engine Volvo TAD880GE
Model generator Leroy Somer LSA 44.3L10
Emission Standard Euro Stage V
Standard Options:
- Fuel tank with bund
- Heavy duty base frame with tow bar
- Central lifting eye
- Forklift guides
- Base frame closed at the bottom
- Spark arrestor
- Quick connectors for connection to external tank