Diesel Generator 200 kVA Industrial

G200RS - UR.png
G200RS - UR.png

IDEAL USAGE

Projects that require efficient and reliable temporary power, including industrial locations
 

APPLICATIONS
 

  • Powering locations where permanent electricity supply is not available -such as temporary accommodation, construction or other remote sites
  • Replacing utility power supply to industrial equipment - motors, pumps, conveyors and other equipment
  • Additional power for seasonal increases in demand such as manufacturing, distribution and strorage
     

BENEFITS

  • Telemetry, spark arrestor, automatic engine shut-off valve and multiple generator synchronisation
  • Fuel efficient, proven reliability
  • Robust design
RESOURCES

Diesel Generator 200 kVA Industrial

PERFORMANCE

Power Factor:

3 phase: 0.8
1 Phase: 1

Fuel Consumption:

100% Load Prime       50 Hz    46.20 L/h
75% Load Prime                       37.30 L/h
50% Load Prime                       25.40 L/h
100% Load Standby                 48.50 L/h

100% Load Prime       60 Hz     47.80 L/h
75% Load Prime                       38.00 L/h
50% Load Prime                       26.40 L/h
100% Load Standby                 51.10 L/h

Fuel System:

Diesel Specification                   EN590
Standard Capacity Fuel Tank    515 L

Typical Sound Pressure:

dBa @ 7 50 Hz 68 dBa

 

WEIGHTS AND MEASURES

Weight:

3800 Kg
*Standard build with all fluids except fuel

Dimensions:

2033 mm x 1270 mm x 3800 mm (H x W x L)

Shipping Volume:

Sea Ready: 9.90 m³

ENGINE & ALTERNATOR

Engine:

                                            1500 RPM 1800 RPM
New Output Rating (PRP)        169 kW    194 kW
Net Output Rating (Standby)    187 kW    212 kW

Manufacturer and Model: John Deere - 6066HFU82
Fuel: Diesel
Injection: Direct
Aspiration: Turbo Charged
Cylinders:4
Bore and Stroke:106 x 127 mm
Displacement: 6.80 L
Cooling: Water
Compression Ratio: 18 : 1
Engine Oil Specification: JCB EP 15W40
Engine Oil Capacity: 24:60 L
Coolant Capacity: 11.30 L
Governer: Electronic
Air Filter: Paper Element
Engine Oil Consumption 100%: 0.1% of fuel consumed 
Exhaust Emission After Treatment: None
Emission Standard: Stage IIIA Transition

Alternator UCI 274H:

Poles: 4
Winding Connections: Star
Insulation: Class H
Encloser: IP23
Exciter System: Self Regulating brushless
Voltage Regulator: AVR 
Steady State Votlage Regulator:  +/- 1%
Bearing: Single bearing sealed
Coupling: Flexible doc
Cooling: Direct drive centrifugal fan

Starting System:

Battery Capacity: 850 Ah
Number of Batteries: 1
Auxillery Voltage: 12 V

Air System:

Intake Air Flow 100% Standby: 50 Hz 597 m³/h 
Radiator Cooling Airflow: 5.6 m³/h

 

Exhaust System:

Maximum temperature:                     50 Hz    600 °C
Exhaust Gas Flow 100% Standby:                 30.12 m³/min
Maximum Allowed Back Pressure:                 7.50 kPa
Exhaust Discharge Size:                                100 mm
 

 

DATA SHEET