Generator 250 kVA Stage V


IDEAL USAGE
Projects that require efficient and reliable temporary power, including industrial locations.
APPLICATIONS
- Temporary Power supply for projects for which connecting to an electricity grid isn’t available, such as temporary accommodations and construction or other remote sites.
- Backup or bypass power supply during (maintenance) works in order to keep (industrial) equipment operational.
- Additional power for (seasonal) increases in demand.
- Standalone power supply for secondary processes.
BENEFITS
- Telemetry and multiple generator synchronisation
- Fuel efficient, proven reliability
- Robust design
Generator 250 kVA Stage V
Electrical Features:
Main circuit breaker 400A
Earth Leakage switch 30 mA adjustable
Connections 1x 16 A 3p, 230 V CEE connector
2x 125 A 5p, 400 V CEE connector
Busbar
1x Powersave connectors L1, L2, L3, N & PE
Fuel Consumption:
70% Load Prime 37.9 L/h
70% Load Prime (AdBlue Tank) 2.8 L/h
Autonomy:
70% Load Prime 26 hours
70% Load Prime (AdBlue Tank) 25 hours
Typical Sound Pressure:
LpA (7 m) 67 dBa
Communication and Control:
Featuring: Automatic load-sharing mode
Automatic pre-heating
Automatic start via timer or external contact
Oil pressure alarm
High temperature alarm
Fuel level alarm
Bund level alarm
Overload alarm
Readable data: Alarms and warnings
Fuel level
Engine running hours
Frequency
Voltage per phase
Amperage per phase
Power in kW and kWh
Next maintenance
Dimensions:
4250 mm x 2000 mm x 2230 mm (L x W x H)
Weight:
5500 kg
Capacity Fuel Tank:
1000 L
Capacity AdBlue Tank:
70 L
Engine:
Power 250 kVA
Voltage 230/400 V 50 Hz
Manufacturer and Model Bruno GX275S-V Loadsharing
Model engine Scania DC09320A0261
Model generator Leroy Somer LSA 46.3S5
Emission Standard Euro Stage V
Standard Options:
- Fuel tank with bund
- Heavy duty base frame with tow bar
- Central lifting eye
- Forklift guides
- Base frame closed at the bottom
- Spark arrestor
- Quick connectors for connection to external tank