Generator 150 kVA Loadsharing

IDEAL USAGE

Projects that require efficient and reliable temporary power, including industrial locations. 
 

APPLICATIONS

  • Temporary Power supply for projects for which connecting to an electricity grid isn’t available, such as temporary accommodations and construction or other remote sites.
  • Backup or bypass power supply during (maintenance) works in order to keep (industrial) equipment operational.
  • Additional power for (seasonal) increases in demand.
  • Standalone power supply for secondary processes.
     

BENEFITS

  • Telemetry and multiple generator synchronisation
  • Fuel efficient, proven reliability
  • Robust design
RESOURCES

Generator 150 kVA Loadsharing

PERFORMANCE

Electrical Features:

Main switch                                 CB200A
Main circuit breaker                    300 mA adjustable
Connections                                1x 63 A 5p, CEE connector
                                                     1x 125 A 5p, CEE connector
                                                     500 A Powerlock connectors L1, L2, L3, N & Earth
                                                     Busbar 
                                                     MSA+ / Amphenol 3p for Remote Emergency Stop /                                                            gas detection                    

Fuel Consumption:

70% Load Prime                           21.3 / 25.6 L/h                                                 

Autonomy:

70% Load Prime                           10 / 12 hours

Typical Sound Pressure:

dBa @ 7                                       67 dBa

Communication and Control:

Control Panel:                             Deepsea 8610
Featuring:                                    Load-sharing
                                                    Automatic start via timer or external contact
                                                    Oil pressure alarm
                                                    Fuel level alarm
                                                    Bund level alarm
                                                    Overload alarm
Readable data:                            Fuel level
                                                    Engine running hours
                                                    Frequency
                                                    Voltage per phase
                                                    Amperage per phase
                                                    Power in kW and kWh
                                                    Next maintenance
                                                    Fuel tank with bund

WEIGHT AND MEASUREMENTS

Dimensions:

3380 mm x 1130 mm x 1850 mm (L x W x H)

Weight:

2870 kg

Capacity Fuel Tank:

270 L

ENGINE AND OPTIONS

Engine:

Power                                                  150 kVA
Voltage                                                230/400 V 50 Hz
Manufacturer and Model                    Bruno                  FX173V / GX181F
Model engine                                      Volvo                  TAD751GE
Model generator                                 Leroy Somer       LSA 44.3L10
Emission Standard                               Euro Stage IIIA

Standard Options:

  • Heavy duty base frame with tow bar
  • Central lifting eye
  • Forklift guides
  • Base frame closed at the bottom
  • Spark arrestor
  • Quick connectors for connection to external tank
DATA SHEET